10.16 - Final Quick Reference
Module: Universal Review and Mock Examinations
Purpose: Final compact review for EPA Section 608 Universal certification preparation
Covers: Core, Type I, Type II, and Type III high-priority facts from Modules 1–10
Current regulatory verification basis: August 14, 2026
Use: Final rapid review only. If a rule or condition is unclear, return to the detailed course section rather than memorizing an isolated number.
1. Universal Master Table
| Item | Core | Type I | Type II | Type III |
|---|---|---|---|---|
| Primary scope | Common environmental, regulatory, recovery, safety, and refrigerant knowledge | Small appliances | Medium-, high-, and very-high-pressure appliances | Low-pressure appliances |
| Typical equipment | Applies across all types | Refrigerator, window A/C, dehumidifier, qualifying packaged terminal unit | Split system, heat pump, rooftop unit, walk-in, supermarket rack | Low-pressure centrifugal or absorption chiller |
| Classification key | Common knowledge | Factory manufactured + factory charged + factory hermetically sealed + 5 lb or less | Refrigerant pressure category; not Type I or Type III | Refrigerant saturation pressure below 45 psia at 104°F |
| Recovery emphasis | Recover, recycle, reclaim; equipment and cylinder fundamentals | 80% / 90% recovery or 4 in. Hg vacuum alternative | Bulk liquid first where practical, vapor finish, pressure-rebound check | Liquid first, vapor second, water/freezing control |
| Evacuation / removal requirement | Know pressure/vacuum units and current Table 1 logic | Percentage requirement or 4 in. Hg vacuum alternative | Current Table 1: 0 / 4 / 10 / 15 in. Hg vacuum, depending on conditions | 25 mm Hg absolute |
| Major-repair relevance | Know definition and service-practice rules | Type I recovery/service procedures control | Major-repair definition and Table 1 are high priority | Major-repair and low-pressure service provisions apply |
| Leak-repair emphasis | Know applicability and current-vs-historical distinction | Not defined by Type I classification | Current Section 608 ODS leak-repair rules are frequently tested | Same federal applicability logic; Type III classification alone does not create leak-repair applicability |
| Charging emphasis | Correct refrigerant, avoid contamination, blend handling | Follow appliance/refrigerant procedure | Follow manufacturer procedure; blend composition matters | From deep vacuum: vapor first, liquid later |
| Primary safety emphasis | PPE, ventilation, cylinders, nitrogen, fire/electrical hazards | Frostbite, cylinder/access safety | High pressure, compressor/discharge safety, relief protection | Freeze risk, pressure relief, machinery-room and water-side hazards |
| Common trap | Correct fact used in wrong context | ≤5 lb alone is not enough | 15 lb, 50 lb, and 200 lb are different rules | 25 mm Hg absolute is not 25 in. Hg vacuum |
Universal Certification Relationship
CORE
+
TYPE I
+
TYPE II
+
TYPE III
→ UNIVERSAL
Core is the common examination section. It is not a fourth appliance type.
2. Classification First
Before selecting a recovery rule, evacuation value, or service procedure:
1. IDENTIFY THE APPLIANCE
2. CHECK MVAC / MVAC-LIKE STATUS
3. CHECK THE COMPLETE SMALL-APPLIANCE DEFINITION
4. IF NOT TYPE I, DETERMINE PRESSURE CATEGORY
5. IDENTIFY THE SERVICE CONDITION
6. THEN SELECT THE RULE
Fast Classification
Factory manufactured
+
factory charged
+
factory hermetically sealed
+
≤5 lb refrigerant
→ TYPE I
Medium / high / very-high pressure
→ TYPE II
Low pressure
→ TYPE III
Type I + Type II + Type III
→ UNIVERSAL
3. Core Final Summary
Environmental and Regulatory
Clean Air Act Section 608
→ U.S. stationary refrigerant-management program
Montreal Protocol
→ international ozone-depleting-substance control framework
Stratospheric ozone
→ protects against harmful UV
CFC / HCFC
→ contain chlorine
→ nonzero ODP
HFC / HFO
→ no chlorine
→ zero ODP
Zero ODP does not mean zero GWP, zero flammability, zero toxicity, or permission to vent.
Venting
DO NOT knowingly vent covered refrigerant
during maintenance, service, repair, or disposal
Limited permitted releases include properly defined de minimis releases associated with good-faith recovery and specific exempt substitutes/end uses.
Nitrogen alone
→ may be released after proper testing
Nitrogen + covered refrigerant
→ do not intentionally vent the mixture
Recover, Recycle, Reclaim
RECOVER
→ REMOVE + STORE
RECYCLE
→ CLEAN FOR PERMITTED REUSE
RECLAIM
→ REPROCESS + VERIFY PURITY
Recovery Equipment
SYSTEM-DEPENDENT
→ depends on appliance components and/or refrigerant pressure
SELF-CONTAINED
→ has its own independent recovery means
FULL CHARGE >15 lb
→ ordinary system-dependent equipment prohibited
→ unless permanently attached as a pump-out unit
Recovery Cylinders
RECOVERY CYLINDER
→ refillable
DISPOSABLE CYLINDER
→ do not refill
→ do not use for recovery
Use a scale and do not overfill.
Project exam-preparation concept:
80% maximum fill concept
Any lower manufacturer, transportation, or refrigerant-specific limit controls actual field use.
Pressure and Vacuum
psig
→ referenced to atmosphere
psia
→ referenced to perfect vacuum
0 psig
≠
0 psia
in. Hg vacuum
→ larger number = deeper vacuum
mm Hg absolute / microns
→ smaller number = deeper vacuum
Nitrogen Safety
Use:
DRY NITROGEN
+
PRESSURE REGULATOR
+
DOWNSTREAM RELIEF PROTECTION
Never use oxygen or compressed air for refrigerant-system pressure testing.
Section 608 Versus Section 609
SECTION 608
→ stationary appliances
SECTION 609
→ MVAC service for consideration
Universal Section 608 certification does not replace Section 609 certification for paid MVAC service.
Vehicle-mounted cargo refrigeration is not automatically an MVAC.
4. Type I Final Summary
Small-Appliance Definition
All four conditions are required:
FACTORY MANUFACTURED
+
FACTORY CHARGED
+
FACTORY HERMETICALLY SEALED
+
5 lb OR LESS
≤5 lb ALONE
≠
TYPE I
Type I Recovery Requirements
| Condition | Requirement |
|---|---|
| Recovery/recycling equipment manufactured before Nov. 15, 1993 | 80% recovery |
| On/after Nov. 15, 1993 + appliance compressor functional | 90% recovery |
| On/after Nov. 15, 1993 + appliance compressor nonfunctional | 80% recovery |
| Alternative | 4 in. Hg vacuum |
Remember:
THE DATE APPLIES TO THE RECOVERY EQUIPMENT
NOT THE APPLIANCE
THE COMPRESSOR CONDITION REFERS TO
THE APPLIANCE COMPRESSOR
Operating Compressor
OPERATING COMPRESSOR
→ compressor assists refrigerant movement
→ high-side recovery emphasis
Failed Compressor
FAILED COMPRESSOR
→ no compressor pumping assistance
→ high + low access as needed
Controlled heat may help release trapped refrigerant.
Never use an open flame.
Access Fittings
PROCESS STUB
→ tubing
PIERCING / SOLDERLESS ACCESS FITTING
→ temporary service access
Current Type I exam emphasis:
REMOVE TEMPORARY SOLDERLESS FITTING
AFTER SERVICE
→ restore / reseal tubing
→ leak check
Disposal
Final processor:
RECOVER REMAINING REFRIGERANT
OR
VERIFY ACCEPTABLE PRIOR RECOVERY
Prior-recovery signed statement:
NAME
+
ADDRESS
+
DATE
Required final-processor statements/contracts:
KEEP 3 YEARS
A sticker alone is not sufficient prior-recovery verification.
5. Type II Final Summary
Type II Scope
MEDIUM
+
HIGH
+
VERY HIGH PRESSURE
→ TYPE II
Pressure Categories
| Category | Current Classification |
|---|---|
| Low | <45 psia at 104°F |
| Medium | 45–170 psia at 104°F |
| High | 170–355 psia at 104°F |
| Very high | Critical temperature below 104°F, or liquid-phase saturation pressure >355 psia at 104°F |
High-pressure appliance classification is not the same as the high side of a refrigeration system.
Recovery Sequence
PREPARE SYSTEM + CYLINDER
→ RECOVER ACCESSIBLE BULK LIQUID FIRST
→ RECOVER REMAINING VAPOR
→ REACH REQUIRED ENDPOINT
→ ISOLATE
→ CHECK PRESSURE REBOUND
Pressure rebound can come from:
- Refrigerant evaporating from cold components.
- Refrigerant leaving compressor oil.
- Refrigerant trapped in isolated sections.
FIRST LOW PRESSURE READING
≠
AUTOMATICALLY COMPLETE
System-Dependent Restriction
FULL CHARGE >15 lb
→ no ordinary system-dependent recovery equipment
→ unless permanently attached pump-out unit
The rule uses full charge, not the amount remaining after a leak.
Type II Evacuation Table
Recovery Equipment Manufactured On or After November 15, 1993
| Appliance | Required Level |
|---|---|
| Very-high pressure | 0 in. Hg vacuum |
| High pressure, <200 lb full charge | 0 in. Hg vacuum |
| High pressure, ≥200 lb full charge | 10 in. Hg vacuum |
| Medium pressure, <200 lb full charge | 10 in. Hg vacuum |
| Medium pressure, ≥200 lb full charge | 15 in. Hg vacuum |
Recovery Equipment Manufactured Before November 15, 1993
| Appliance | Required Level |
|---|---|
| Very-high pressure | 0 in. Hg vacuum |
| High pressure, <200 lb full charge | 0 in. Hg vacuum |
| High pressure, ≥200 lb full charge | 4 in. Hg vacuum |
| Medium pressure, <200 lb full charge | 4 in. Hg vacuum |
| Medium pressure, ≥200 lb full charge | 4 in. Hg vacuum |
Major Maintenance, Service, or Repair
Major if removing:
- Compressor.
- Condenser.
- Evaporator.
- Auxiliary heat-exchange coil.
Also major if:
OPENING >4 in² OF FLOW AREA
+
OPEN >15 MINUTES
FILTER-DRIER REPLACEMENT
≠
AUTOMATICALLY MAJOR
Special Service-Pressure Concepts
When all regulatory conditions are satisfied:
QUALIFYING NON-MAJOR OPENING
→ NO HIGHER THAN 0 psig
LEAK PREVENTS NORMAL TABLE 1 ENDPOINT
→ isolate where possible
→ non-leaking portion to Table 1
→ leaking portion to lowest attainable
→ not above 0 psig
SPECIAL OIL-CHANGE PROVISION
→ NO HIGHER THAN 5 psig
Current Section 608 ODS Leak-Repair Triggers
For qualifying appliances containing 50 lb or more of applicable ozone-depleting refrigerant:
| End Use | Current Trigger |
|---|---|
| Industrial process refrigeration | 30% |
| Commercial refrigeration | 20% |
| Comfort cooling | 10% |
| Other qualifying appliances | 10% |
35% / 15%
→ HISTORICAL
→ NOT THE CURRENT SECTION 608 TABLE
Do not confuse the Section 608 ODS framework with the separate current AIM Act HFC leak-repair framework.
Type II Safety
RECIPROCATING COMPRESSOR
+ CLOSED DISCHARGE SERVICE VALVE
→ DO NOT ENERGIZE
HERMETIC COMPRESSOR
+ DEEP VACUUM
→ DO NOT ENERGIZE
HIGH HEAD PRESSURE
→ diagnose cause
→ do not bypass safety control
Verify pressure ratings for recovery machines, hoses, gauges, cylinders, and fittings on very-high-pressure systems.
6. Type III Final Summary
Low-Pressure Classification
<45 psia at 104°F
→ LOW PRESSURE
→ TYPE III
Many low-pressure chillers operate below atmospheric pressure.
Therefore:
AIR + MOISTURE
→ CAN LEAK INTO THE SYSTEM
Purge Unit
PURGE UNIT
→ removes noncondensables
→ minimizes refrigerant loss
Frequent purge operation can indicate air infiltration.
The purge unit is not the recovery machine for the entire chiller charge.
Leak Testing
Type III exam-preparation value:
10 psig
→ low-pressure leak-test maximum
This is an exam-preparation maximum, not a universal target pressure for every chiller.
Recovery Sequence
LIQUID FIRST
→ VAPOR SECOND
→ REQUIRED ENDPOINT
→ ISOLATE + CHECK REBOUND
No visible liquid does not mean recovery is complete.
Freeze Prevention
As refrigerant pressure falls:
SATURATION TEMPERATURE FALLS
→ WATER CAN FREEZE
During normal deep recovery:
CIRCULATE / MANAGE WATER AS REQUIRED
If a tube leak is suspected under the Type III exam procedure:
DRAIN EVAPORATOR WATER SIDE
+
DRAIN CONDENSER WATER SIDE
BEFORE RECOVERY
Refrigerant in Oil
Refrigerant can remain dissolved in oil and come out of solution as pressure falls.
Traditional Type III exam value:
130°F
→ oil-heating value before oil removal
Current oil-change pressure provision:
NO HIGHER THAN 5 psig
Charging
From a deep vacuum:
VAPOR FIRST
→ pressure rises
→ saturation temperature rises
→ freeze risk decreases
→ LIQUID LATER when approved
For blends, distinguish:
REMOVE BLEND FROM SOURCE AS LIQUID
from:
INTRODUCE VAPOR FIRST INTO
A DEEPLY EVACUATED LOW-PRESSURE CHILLER
Both can be correct in the same controlled charging procedure.
Type III Evacuation Requirement
25 mm Hg absolute
for the current normal low-pressure Table 1 refrigerant-removal endpoint.
25 mm Hg absolute
≠
25 in. Hg vacuum
Traditional Type III Exam Values
10 psig
→ leak-test maximum
10 psig
→ recovery-unit high-pressure cutout
15 psig
→ low-pressure recovery-vessel rupture-disc value
130°F
→ oil heating
5 psig
→ current oil-change opening provision
25 mm Hg absolute
→ normal low-pressure evacuation endpoint
Do not generalize the 15 psig recovery-vessel rupture-disc value into a universal chiller pressure-relief rating.
Type III Safety
REFRIGERANT MONITOR
→ refrigerant concentration
OXYGEN MONITOR
→ oxygen concentration
MACHINERY ROOM
≠
AUTOMATICALLY OSHA CONFINED SPACE
Before water-side service:
STOP / ISOLATE ENERGY
→ RELIEVE PRESSURE
→ VERIFY SAFE CONDITION
A stopped pump does not prove that water-side pressure is zero.
7. Highest-Priority Numbers
Memorize every number with its concept, condition, and unit.
| Number / Value | What It Controls |
|---|---|
| 2 lb or less | Qualifying DIY MVAC small-can sales exception, with required unique fitting and self-sealing valve |
| 5 lb or less | Charge limit within the complete Type I small-appliance definition |
| >15 lb full charge | Ordinary system-dependent recovery-equipment restriction unless permanent pump-out |
| ≥50 lb | Current Section 608 ODS leak-repair applicability threshold for qualifying appliances |
| 200 lb | Type II evacuation-table charge boundary |
| 45 / 170 / 355 psia @ 104°F | Pressure-category boundaries / very-high criterion |
| 80% / 90% | Type I recovery percentages under the applicable conditions |
| 4 in. Hg vacuum | Type I alternative recovery endpoint; also appears in pre-1993 Table 1 rows |
| 0 / 10 / 15 in. Hg vacuum | Major current post-1993 Type II Table 1 endpoints |
| 25 mm Hg absolute | Current Type III Table 1 endpoint |
| 30% / 20% / 10% | Current Section 608 ODS leak-rate triggers |
| >4 in² + >15 min | Numerical major-repair criterion |
| 0 psig | Qualifying non-major / leaking-section ceiling when applicable |
| 5 psig | Current special oil-change pressure provision |
| 10 psig | Type III leak-test exam maximum; separately, recovery-unit cutout exam value |
| 15 psig | Type III recovery-vessel rupture-disc exam value |
| 130°F | Traditional Type III oil-heating exam value |
| 3 years | Common retention period for several Section 608 records |
| Nov. 15, 1993 | Recovery/recycling-equipment date boundary |
The Three Charge Numbers Most Often Confused
5 lb
→ TYPE I SMALL-APPLIANCE DEFINITION
15 lb
→ SYSTEM-DEPENDENT RECOVERY-EQUIPMENT RULE
50 lb
→ CURRENT SECTION 608 ODS LEAK-REPAIR APPLICABILITY
200 lb
→ TYPE II EVACUATION-TABLE BOUNDARY
8. Current Leak-Rule Separation
Section 608 ODS Framework
For qualifying appliances:
≥50 lb applicable ODS refrigerant
Current trigger rates:
IPR 30%
COMMERCIAL 20%
COMFORT 10%
OTHER 10%
Separate AIM Act HFC Framework
The project also identifies a separate current federal HFC leak-repair framework under 40 CFR Part 84.
Do not combine the two programs.
Key distinction:
SECTION 608 ODS RULE
≠
AIM ACT HFC RULE
When an exam question identifies the regulatory framework, use the conditions belonging to that framework.
9. Commonly Confused Terms
| Do Not Confuse | Correct Distinction |
|---|---|
| Recover / recycle / reclaim | Remove / clean / reprocess and verify |
| psig / psia | Atmosphere reference / perfect-vacuum reference |
| in. Hg vacuum / mm Hg absolute | Larger-deeper / smaller-deeper |
| Core / Universal | Common knowledge / Types I + II + III |
| Type II / Section 609 | Stationary medium/high/very-high pressure / MVAC service |
| High-pressure appliance / high side | Whole appliance category / circuit location |
| Low-pressure appliance / low side | Whole appliance category / circuit location |
| Functional compressor / compressor present | Must actually be able to assist recovery |
| Recovery cylinder / disposable cylinder | Refillable / one-way |
| Major repair / any repair | Specific regulatory definition / general service work |
| Non-major / no evacuation rule | Non-major work still requires checking the applicable provision |
| Current leak rates / historical rates | 30/20/10 / legacy 35/15 framework |
| EPA requirement / provider policy | Federal rule / test-administration procedure |
| Recovery endpoint / dehydration target | Refrigerant-removal rule / technical moisture-removal target |
10. Highest-Priority Universal Exam Traps
Trap 1 - Correct Number, Wrong Rule
15 lb
50 lb
200 lb
are not interchangeable.
Always identify what the number controls.
Trap 2 - Correct Rule, Wrong Appliance
A Type I recovery percentage is not a Type II evacuation requirement.
A Type III vacuum value is not a Type II value.
Trap 3 - Charge Alone Determines Type I
≤5 lb
≠
automatically small appliance
All four small-appliance conditions are required.
Trap 4 - November 15, 1993 Means Appliance Date
Wrong.
For the recovery requirements emphasized in this course:
NOV. 15, 1993
→ RECOVERY / RECYCLING EQUIPMENT DATE
Trap 5 - Historical Leak Rates Used as Current
35% / 15%
→ historical
Current Section 608 ODS trigger table:
30% / 20% / 10%
Trap 6 - High Side Means Type II
Wrong.
HIGH SIDE
→ refrigeration-cycle location
TYPE II
→ appliance certification category
Trap 7 - Low Side Means Type III
Wrong.
A Type II system also has a low side.
Trap 8 - Failed Compressor Removes Recovery Requirement
Wrong.
The recovery method changes; the recovery requirement remains.
Trap 9 - No Visible Liquid Means Recovery Complete
Wrong.
Vapor, dissolved refrigerant, or trapped refrigerant can remain.
Trap 10 - Deep-Vacuum Type III Charging Starts With Liquid
Wrong.
VAPOR FIRST
→ LIQUID LATER
Trap 11 - 25 mm Hg Absolute Equals 25 in. Hg Vacuum
Wrong.
The units and reference points are different.
Trap 12 - Purge Unit Is a Recovery Machine
Wrong.
The purge unit removes noncondensables while minimizing refrigerant loss.
Trap 13 - Provider Policy Is EPA Law
Wrong.
Time limits, attempt counts, waiting periods, software, and credential-delivery procedures are provider-specific.
Trap 14 - Universal Includes Section 609
Wrong.
Universal is:
TYPE I + TYPE II + TYPE III
Paid ordinary MVAC service still requires the applicable Section 609 credential.
Trap 15 - Good Practice Automatically Equals the Federal Minimum
A manufacturer or technical service procedure may require a deeper vacuum or additional steps beyond the Section 608 refrigerant-removal endpoint.
Know what the question is asking.
11. Five-Step Question Method
For every question:
1. WHAT APPLIANCE / SECTION IS THIS?
2. WHAT CONDITION CONTROLS?
3. WHAT RULE OR PHYSICAL PRINCIPLE APPLIES?
4. WHAT UNIT / DATE / THRESHOLD IS USED?
5. WHICH CHOICE ANSWERS THE EXACT QUESTION?
Watch especially for:
NOT
EXCEPT
MINIMUM
MAXIMUM
FIRST
LAST
CURRENT
HISTORICAL
REQUIRED
PROHIBITED
A distractor is often a true statement that belongs to a different appliance, condition, date, or regulatory program.
12. Final Exam-Day Reading Checklist
Immediately before the official examination, read this section once.
Knowledge
- I can classify Type I, Type II, and Type III equipment before choosing a procedure.
- I know the complete small-appliance definition.
- I know the
5 / 15 / 50 / 200 lbdistinctions. - I know the Type I
80% / 90% / 4 in. Hg vacuumrules. - I know the Type II current evacuation table.
- I know the Type III 25 mm Hg absolute requirement.
- I know current Section 608 ODS leak rates are 30% / 20% / 10%.
- I can separate current rules from historical values.
- I can separate EPA regulations from provider policies.
- I have no unresolved high-priority safety or regulatory errors.
Test Setup
- I have confirmed the certifying organization is currently EPA approved.
- I have read the provider’s current candidate instructions.
- I know the current time limit and scoring / section-credit method.
- I know what materials, calculator, P-T chart, or scratch materials are permitted.
- Identification is ready.
- Account login works.
- Camera, microphone, device, and internet are ready if remotely proctored.
- The testing area is quiet and compliant.
- Unauthorized notes and devices are removed.
During the Exam
- Read the entire stem before looking for a familiar number.
- Identify the appliance or certification section.
- Mark
NOT,EXCEPT,MINIMUM,MAXIMUM,FIRST, and similar controlling words mentally. - Check units.
- Eliminate choices that belong to another Type or another condition.
- Do not spend excessive time on one question.
- Return to uncertain questions if time remains.
- Change an answer only for a specific technical or reading reason.
- Do not use outside help or unauthorized materials.
Final Reminder
CLASSIFY FIRST
→ FIND THE CONTROLLING CONDITION
→ APPLY THE CORRECT RULE
→ CHECK THE UNIT
→ ANSWER ONLY WHAT WAS ASKED
13. Project Readiness Standard
Before the official Universal attempt:
CORE ≥22/25
TYPE I ≥22/25
TYPE II ≥22/25
TYPE III ≥22/25
on:
TWO SEPARATE
CLOSED-BOOK
CUMULATIVE ATTEMPTS
and:
ZERO UNRESOLVED P1 ERRORS
This is the project’s preparation standard, not the federal passing-score rule.
If any section has not met the target, return to:
10.10 - Error Analysis and Remediation.md10.13 - Optional Remediation Examination.md10.14 - Official Examination Readiness Checklist.md
14. Final Universal Memory Map
CORE
→ environment + regulation + refrigerants
→ recovery + cylinders + evacuation + safety
TYPE I
→ small appliance
→ all four definition conditions
→ 80 / 90 / 4
→ operating vs failed compressor
TYPE II
→ medium + high + very high
→ 45 / 170 / 355
→ liquid first where practical
→ 15 / 50 / 200 are different rules
→ 0 / 4 / 10 / 15 evacuation values
TYPE III
→ low pressure
→ air + moisture can leak IN
→ purge
→ liquid first / vapor second recovery
→ freeze prevention
→ vapor-first charging
→ 25 mm Hg absolute
UNIVERSAL
→ CORE + TYPE I + TYPE II + TYPE III
FINAL EXAM HABIT
→ CLASSIFY
→ CONDITION
→ RULE
→ UNIT
→ ANSWER
References
Current Regulatory and EPA Sources
-
U.S. Environmental Protection Agency, Section 608 Technician Certification Requirements, project verification August 14, 2026.
-
U.S. Environmental Protection Agency, Section 608 Test Topics, project verification August 14, 2026.
-
U.S. Environmental Protection Agency, Required Level of Evacuation of Appliances, project verification August 14, 2026.
-
U.S. Environmental Protection Agency, Stationary Refrigeration Service Practice Requirements, project verification August 14, 2026.
-
U.S. Environmental Protection Agency, Stationary Refrigeration Leak Repair Requirements, project verification August 14, 2026.
-
Electronic Code of Federal Regulations, 40 CFR Part 82, Subpart F - Recycling and Emissions Reduction, project verification August 14, 2026.